Modbus Function Codes and Exception Codes Explained (With Kotlin Examples)

Short answer: the function code tells the device what to do. The common ones are 3 (read holding registers), 4 (read input registers), 6 (write one register) and 16 (write many registers). If something is wrong, the device replies with the same function code plus 0x80 and a one-byte exception code.

Common function codes

Code Name Use
01 Read coils Read on/off outputs
02 Read discrete inputs Read on/off inputs
03 Read holding registers Read settings and values (most common)
04 Read input registers Read measured, read-only values
05 Write single coil Switch one output
06 Write single register Change one setting
15 (0x0F) Write multiple coils Switch many outputs
16 (0x10) Write multiple registers Change many settings

Many inverters and meters put live measurements in input registers (function 4) and settings in holding registers (function 3). Your manual says which.

Exception responses

If a request fails, the reply is: address, function code with the high bit set (for example 0x83 for a failed function 3), an exception code, then the CRC. It is always 5 bytes.

Code Meaning Usual cause
01 Illegal function Device does not support that function
02 Illegal data address Register address does not exist, or an off-by-one
03 Illegal data value Bad count or a value outside the allowed range
04 Server (slave) device failure Device could not complete the request

Detecting an exception in Kotlin

sealed interface ModbusResult {
    data class Ok(val registers: List<Int>) : ModbusResult
    data class Error(val function: Int, val code: Int) : ModbusResult
}

fun parseResponse(resp: ByteArray): ModbusResult {
    val function = resp[1].toInt() and 0xFF
    if (function and 0x80 != 0) {
        return ModbusResult.Error(function and 0x7F, resp[2].toInt() and 0xFF)
    }
    val n = resp[2].toInt() and 0xFF
    val regs = (0 until n / 2).map { i ->
        ((resp[3 + i * 2].toInt() and 0xFF) shl 8) or (resp[4 + i * 2].toInt() and 0xFF)
    }
    return ModbusResult.Ok(regs)
}

Check the CRC first, as shown in our Modbus RTU basics post, then check the function byte.

Tips

  • Exception 02 is often an off-by-one: some manuals number registers from 1, the protocol address starts at 0.
  • Do not write to a holding register unless you know what it does; some settings affect the hardware.

FAQ

What is the difference between holding and input registers?

Holding registers can be read and written. Input registers are read-only, usually measurements.

What does 0x83 mean?

It is a failed function 3 request (0x03 plus 0x80); the next byte is the exception code.

Register maps differ by manufacturer. Always confirm addresses, scaling and word order in your device manual.